Retrofit of a wet cooling tower in order to reduce water and fan power consumption using a wet/dry approach

Journal: Applied Thermal Engineering (13594311)Year: 2017Volume: 125Issue: Pages: 1002 - 1014
Taghian-Dehaghani S.Ahmadikia H.a

Abstract

A Parallel Path Wet/Dry configuration and a high-precision airflow regulation method are implemented in order to retrofit an existing wet cooling tower. The modifications are intended to reduce water requirements and fan power consumption of a 12-cell wet tower. The proposed method of airflow control takes advantage of fans with variable frequency drive to regulate airflow with high accuracy. A number of simulations are carried out to predict different operating factors of the wet and hybrid towers. Experimentally obtained values of water consumption demonstrate the validity of those obtained using the computer simulations. According to the results, the accurate airflow control prevents sudden fluctuations in requisite fan power and water consumption rate and causes up to 64.6% decrease in fan power consumption. The results reveal that using the proposed wet/dry approach results in an average 9.4% decrease in water consumption. Given the relatively low degree of modifications made to the original wet tower and preserving the condenser operating condition, the accomplished amount of water conservation is satisfactory. © 2017 Elsevier Ltd


Author Keywords

Airflow regulationHybrid cooling towerPower consumptionWater conservationWet cooling tower

Other Keywords

AirCoolingElectric power utilizationRetrofittingVariable speed drivesWater conservationAirflow regulationFan power consumptionHybrid coolingOperating conditionVariable frequency drivesWater consumption rateWater requirementsWet cooling towerCooling towers