Type: Conference paper
Impact of load power factor on sympathetic inrush current
Journal: 2025 29th International Computer Conference, Computer Society of Iran, CSICC 2025 ()Year: 2016Volume: Issue: Pages: 1416 - 1421
DOI:10.1109/IranianCEE.2016.7585743Language: English
Abstract
This paper investigates the impact of load power factor on sympathetic inrush current. Sympathetic inrush current is caused by the voltage drop across the system resistance due to energizing current of the parallel adjacent transformer. It may cause the protection system to mal-trip and the transformer outage. The presented model is validated by simulation using DIgSILENT. The simulation results show that sympathetic inrush current's magnitude depends on the load power factors. This dependency is illustrated and analyzed, which gives deeper insight into sympathetic inrush current and transformer protection. © 2016 IEEE.
Author Keywords
DIgSILENTinductive loadInrush currentload power factorsympathetic inrush current
Other Keywords
Electric equipment protectionElectric power factorDIgSILENTIn-rush currentInductive loadsLoad power factorSympathetic inrush currentTransformer protection